T-100

Overview

The nVent RAYCHEM T-100 connection kit serves as an above-insulation splice or tee kit for up to three RAYCHEM BTV, QTVR, XTV, KTV, or VPL industrial parallel heating cables. It is approved by FM, CSA, and PTB for use in hazardous locations.

Relevant applications include:

  • process temperature maintenance
  • pipe freeze protection
  • tank heating

Industries Served:
Chemical and Pharmaceutical
Food and Beverage
Marine
Mining
Oil and Gas
Power



YouTube Video:
RAYCHEM T-100 Splice/Tee Kit Installation Video

Technical Specifications

  1. All connection kits used to terminate heating cables, including power connectors, splices, tees, and connectors shall be approved for the respective area classification and approved as a system with the particular type of heating cable in use. Under no circumstances shall terminations be used which are manufactured by a vendor other than the cable manufacturer.
  2. In order to keep connections dry and corrosion resistant, connection kits shall be constructed of nonmetallic, electrostatic, charge-resistant, glass-filled, engineered polymer enclosure rated NEMA 4X. The connection kit stand shall allow for up to four inches (100 mm) of thermal insulation.
  3. The connections are made with insulated crimp.
  4. The connection kit shall use cold-applied materials and shall not require the use of a heat gun, torch, or hot work permit for installation.
  5. The connection kit shall be rated to a minimum installation temperature of -40°F (-40°C), minimum usage temperature of -60°F (-50°C), and maximum pipe temperature of 500°F (260°C).